Specific design basis
empty

4.115.

Areas in which there is a risk of exposure to radioiodine, in particular in rooms where systems containing radioactive liquid are likely to release significant amounts of radioiodine in accident conditions, should be considered in the design, including the establishment of adequate criteria for the confinement function of these rooms in various accident conditions.

empty

4.116.

The ventilation of areas in which there is a risk of exposure to radioiodine should be designed to contribute to the limitation of radioactive releases.

empty

4.117.

The design of the heating, ventilation and air‑conditioning systems that contribute to the limitation of radioactive releases should ensure that these systems control and limit the discharge of radioactive substances in normal operation, anticipated operational occurrences and accident conditions.

empty

4.118.

The design of the heating, ventilation and air‑conditioning systems that contribute to the limitation of radioactive releases should filter the exhausted air using pre‑filters, HEPA filters and, if necessary, iodine filters before the air is discharged through the stack. The efficiency of the HEPA and iodine filters should be commensurate with the authorized limits on discharges in normal operation and anticipated operational occurrences and with the acceptable limits on discharges during accident conditions.

empty

4.119.

For determining the rate of air renewal, the following conditions should be considered:

  1. Areas where the risk of internal exposure is significant;

  2. Areas where the risk of internal exposure is negligible;

  3. Areas where the risk of internal exposure is not negligible but where the risk of radioiodine releases is negligible.

empty

4.120.

The design of the heating, ventilation and air‑conditioning systems that contribute to the limitation of radioactive releases, in particular the release of radioiodine, should ensure that an adequate level of protection is provided and should take into account wind effects.

empty

4.121.

The design of the heating, ventilation and air‑conditioning systems maintaining the ambient conditions necessary for the operation of items important to safety and for accessibility and habitability (temperature, humidity, acceptable levels of airborne radioactivity level and fresh air) should take into account the basic atmospheric conditions and the extreme atmospheric conditions (e.g. in terms of temperature and humidity and the duration of these conditions) defined for the design of the nuclear power plant.

empty

4.122.

When part of a heating, ventilation and air‑conditioning system supports a safety system in performing its safety function (safety category 1 or 2) in the event of a design basis accident, it should have an appropriate safety classification and meet the corresponding design requirements, such as the following:

  1. The concept of redundancy should be applied in the design to satisfy the single failure criterion.

  2. The system should be powered by the on‑site emergency power supply.

  3. The system should be protected against internal and external hazards. In particular, the redundant trains should be physically separated, and the components should be resistant to seismic loads. More particularly, and unless duly justified, the ventilation system should be designed to prevent explosive gases, toxic gases and heat from external sources from entering buildings containing items important to safety, and intake and exhaust ventilation ducts should be protected against external explosion.

  4. The system should be subject to periodic inspection and testing. Detailed recommendations are provided in IAEA Safety Standards Series No. NS‑G‑2.6, Maintenance, Surveillance and In‑service Inspection in Nuclear Power Plants [18].

  5. Components should be designed, manufactured, commissioned and tested in accordance with acceptable quality standards.

  6. Components should be designed and manufactured in accordance with acceptable design codes.

empty

4.123.

For the interaction of the heating, ventilation system and air‑conditioning systems with fire protection systems, the recommendations provided in paras 2.19, 4.14, 5.10, 5.13, 5.48, 6.8 and 6.9 of NS‑G‑1.7 [4] should be considered.

empty